Doc. # 1-0002603
Date Updated 02-03-2005 Date Created 07-27-2000
Document Type Knowledge Base Related OS
Related Product PCLS-OPC/ADM
How to write data to a datablock in ADAM OPC Server?
Solution:
User can send any outstanding writes to the process hardware by enabling block writes in one or more datablocks. Once you enable this feature, you can enter the following I/O address into a Digital Output block. I/O address syntax: !SEND:DATABLOCK Where DATABLOCK is the name of the datablock you want write to. Specifying a channel or device name does not write out any data. When any value is written to the Digital Output block, it sends a command to the specified datablock and instructs the driver to send the writes to the process hardware. Analog Output blocks are not supported.