Doc. # 1-0000124 | |||
---|---|---|---|
Date Updated | 11-06-2007 | Date Created | 07-27-2000 |
Document Type | Knowledge Base | Related OS | |
Related Product | ADAM-4017/ ADAM-4018/ ADAM-5013/ ADAM-5017/ ADAM-5017H/ ADAM-5018 |
Which version of ADAM-4017/4018 support "read all channels at a time"? | |||
---|---|---|---|
Solution:
The modules with multi-channel (ADAM-4017/4018) can support "#AA" command to let you read all channels data at a time, but you need to check if the version of firmware equal or higher than the version listed below:
Module #AA
ADAM-4017 D1.0
ADAM-4018 D1.4
As to ADAM-5013/5017/5018 they are all supported, and please refer to "#AASi" command.
|