Doc. # 1-0000138 | |||
---|---|---|---|
Date Updated | 11-29-2004 | Date Created | 07-27-2000 |
Document Type | Knowledge Base | Related OS | |
Related Product | PCLD-782/ PCLD-782B |
Does PCLD-782/B can be use to count the pulse? | |||
---|---|---|---|
Solution:
The answer is yes, but you must pay your attention to the width (duty cycle) and frequency of the pulse. The following is for your reference:
A. PCLD-782 with 4N25 optoisolator: (typical)
t(on) => 2.8 us (turn-on time)
t(off) => 4.5 us (turn-off time)
t(r) => 1.2 us (rise time )
t(f) => 1.3 us (fall time )
B. PCLD-782B with 4N35 optoisolator: (typical)
t(on) => 7.5 us (turn-on time)
t(off) => 5.7 us (turn-off time)
t(r) => 3.2 us (rise time)
t(f) => 4.7 us (fall time)
|