Why ADAM-4018 5th Channel occur data drift?
Solution:
The localised heating problem was found before and it caused the reading in ch5 to ch7 being drifting. After some tested, we found the reading will be 1.5 degree C higher than real temperature. In order to correct the reading, firmware in ADAM-4018 will minus the reading by 1.5 degree C, thus reading will close to real value after some time.