Doc. # 1-0003168
Date Updated 01-22-2004 Date Created 07-27-2000
Document Type Knowledge Base Related OS
Related Product ADAM-4017
First reading is error on ADAM-4017?
Solution:
If the firmware version of ADAM-4017 is V1.1 or earlier and the integrated time is set to 60ms (50Hz), the reading of ADAM-4017 will be incorrect some times. Please check the firmware version by ADAM software to confirm this problem. This problem can be solved by setting the integrated time to 50ms (60Hz) or send it back for upgrading the firmware to Rev.1.2.