Doc. # 1-0003186
Date Updated 01-22-2004 Date Created 07-27-2000
Document Type Knowledge Base Related OS
Related Product ADAM-4510
The ADAM-4510 locks when the power source is switching from AC line to generator.
Solution:
By our experience, the ADAM-4510 will lock if data collision happens in it. It means if ADAM-4510 receive data from each ends at the same time, it will lock. When the power source is switching from AC line to generator, a lots of noise may present on data line and ADAM-4510 may lock. In order to solve it, we provide an ehnanced firmware for ADAM-4510 Rev.C1. If the revision number of your ADAM-4510 is C1, we can send a new firmware chip to you for updating. If not, you may need to change the ADAM-4510.