Doc. # 1-110994271
Date Updated 05-04-2006 Date Created 05-04-2006
Document Type Knowledge Base Related OS
Related Product ADAM-4015/ ADAM-4017+/ ADAM-4018+/ ADAM-4019/ ADAM-4024/ ADAM-4051/ ADAM-4055(Do Not Use)/ ADAM-4056S/ ADAM-4056SO/ ADAM-4060/ ADAM-4069/ ADAM-4117/ ADAM-4118/ ADAM-4150/ ADAM-5000/TCP
5000tcp+4000module
Solution:
step 1: Use ADAM-4000 utility to configure ADAM module's communication protocol as "Modbus".And set its address as 3. step 2: Adjust Node ID of ADAM-5000/TCP as 1 and connect ADAM-4000 module to its COM2. step 3: Run ADAM-5000TCP/6000 utility and click this module icon. step 4: Switch to "Network" Page and remember its IP address.(For example 172.18.2.152) step 5: Switch to "RS-485/Modbus/COM-WDT" and change "Parity" setting as "None" and adjust "RTU Frame Timeout" as 100ms. step 6: Click "Apply" and input the password to make those setting active. step 7: Now you can use Modscan or Advantech MOBDUS/TPC OPC Server to verify it. step 8: Input the IP address(172.18.2.152), set Port as 502 and RS-485 address as 3. step 9: Run it and execute scaling setting to get its engineering value. Please also refer to the attached video tutorial for detail.
Download File Release Date Download Site
5000TCP ADAM417p.avi (0) 05-04-2006
  1. Primary
  2. Secondary