How do I setup for Linear Output for Delta DTB or DTC Controller based on incoming temperature? | |||
---|---|---|---|
Solution:
Set PID0 for the following:
P0 = Max Desired Temp
i = 0
d = 0
CoF0 = 0
Set Following Parameters:
HtPd or CLPd = 0
tP-H = Max Desired Temp
tP-L = 0
Setpoint = Max Desired Temp
|