Modbus/TCP to RTU Bridge Setup | |||
---|---|---|---|
Solution:
Modbus/TCP to RTU Bridge Setup
1) Network/IP Settings:
IP Address ................. 192.168.0.159
Default Gateway ............ 192.168.000.001
Netmask .................... 255.255.255.000
2) Serial & Mode Settings:
Protocol ................... Modbus/RTU,Slave(s) attached
Serial Interface ........... 9600,8,N,1,RS485
3) Modem/Configurable Pin Settings:
CP1 ...... RS485 Output Enable
CP2 ...... Not Used
CP3 ...... Not Used
4) Advanced Modbus Protocol settings:
Slave Addr/Unit Id Source .. Modbus/TCP header
Modbus Serial Broadcasts ... Enabled (Id=0 used as broadcast)
MB/TCP Exception Codes ..... No (no response if timeout or no slave)
Char, Message Timeout ...... 01000msec, 05000msec
Serial TX Delay ............ 0010msec
|