Can I use and output to control a non-resistive load?
Solution:
Application is OK if you use RC suppressor. According to data sheet on internal relay of CTA, relay is good for 1200VA switching. So @ 120V, 10AMPS is max allowable for inrush With motor at 0.57A FLA, inrush should be less than 10A. http://www.surplustraders.net/specs/dc536.pdf 892HN-1CH-C NOTE: RC suppressor recommended