How do you connect a 2 wire RTD to the SG2 unit? | |||
---|---|---|---|
Solution:
Please connect the 2-wire RTD probe to terminal 3 and 4, it is the same as 3-wire RTD. Then short terminal 4 and 5 with other wire, it works in this connection. But there is a disadvantage, the DTB can not make the compensation of wire resistance. If the wiring is too long, it might has big offset at input measurement.
|