Doc. # 1-00000375
Date Updated 10-26-2018 Date Created 09-12-2017
Document Type Knowledge Base Related OS
Related Product SG2-10HR-A/ SG2-10KR-A/ SG2-12CR-D/ SG2-12HR-12D/ SG2-12HR-D/ SG2-12HT-D/ SG2-12KR-D/ SG2-20CR-D/ SG2-20HR-12D/ SG2-20HR-A/ SG2-20HR-D/ SG2-20HT-D/ SG2-20KR-A/ SG2-20KR-D/ SG2-20VR-D/ SG2-20VT-D
Can a customer program the 4 Blue arrow buttons on the front of the PLR to perform a function?
Solution:
Yes this can be done. Each button has a label, Z1, Z2, Z3, Z4. So in the ladder logic program if you put Z1 input to output 1. Every time you hit that arrow output 1 will give you a momentary contact closure. You must go into the SG2 software and click on Operation--Module System Setup, under Other Setting check the box that says Z Set and click Set. The 4 blue arrow buttons now can be used as momentary contact closure and no longer will function as directional keys.