How do I configure the 2 port serial MESR units when I have duplicate slave numbers? | |||
---|---|---|---|
Solution:
This example is if you have 4 slaves on each port (slaves 1-4) What we are doing is we are reassigning the slaves on port 2 to be 5-8. So the Modbus master would need to request data from 5-8 in order to get the data. We are basically changing the slave numbers on the 2nd port. On port 1 ID remap do nothing. On Port 2 redirect as shown. Then do this in Slave ID routing
|
|||